Click to rate and give feedback    1 2 3 4 5
How to How to 8/9/2018
Products: WebStation
Functionalities: Alarms
Product version: 2.0

Enabling an Alarm in WebStation

You enable alarms so they change state according to the variables the alarm monitors.

Show More

To enable an alarm in WebStation
  1. In the Alarms pane, click the alarm.

  2. In the Alarm Details box, click Enable alarm .

If you enable an alarm that has been disabled by a user (Disable cause = User), the alarm goes to Normal state for re-evaluation. If you enable an alarm that has been disabled by the System or a shunt variable, the alarm stays disabled.